Fire Compartmentation as per NBC 2016: A Plain Guide
Fire curtain installed above an opening in an office lobby
Fundamentals · 7 min read

Fire Compartmentation as per NBC: How a Building Holds Fire Back

A fire compartment is a promise. It says fire starting in this zone will stay here long enough for people to leave and firefighters to arrive. That promise is kept or broken by small details nobody looks at after handover.

By the Simfy Firesys team·Passive fire protection, Hyderabad
Fire curtain installed above an opening in an office lobby
FundamentalsA compartment is only as good as its weakest opening.
The short answer

Fire compartmentation means dividing a building into zones with fire-resisting walls, floors and doors, so a fire stays in the zone where it starts for a set time. The National Building Code of India 2016, Part 4, sets when compartments are needed and how large they may be. Every opening through a compartment wall or floor must be sealed to keep the rating.

What is fire compartmentation?

Fire compartmentation is the practice of dividing a building into smaller fire zones. Each zone, or compartment, is bounded by walls, floors and doors that resist fire for a set period, often expressed in minutes such as 60, 90 or 120. If a fire starts inside one compartment, the boundary holds it there for that period.

That time is what everything else depends on. It is the time people have to reach a protected staircase. It is the time firefighters have to arrive and set up. It is the time that keeps a fire on one floor from becoming a fire in the whole building. Sprinklers fight the fire. Compartments buy the time.

In India the main reference is the National Building Code of India 2016, Part 4, Fire and Life Safety. It sets when compartmentation is required, how big compartments can be for different types of building, and what fire resistance their boundaries need. We explain how compartments fit into the wider picture in what is passive fire protection.

How big can a compartment be?

NBC sets maximum compartment sizes that depend on the occupancy, such as offices, hospitals, hotels, shops or factories, on the height of the building, and on whether it has sprinklers. Sprinklered buildings are generally allowed larger compartments, because the sprinklers help keep a fire small.

We do not quote a single figure here on purpose. The right number for your building depends on several factors together, and the fire consultant who prepares your fire safety drawings will confirm it. What matters for owners is this: once those compartments are drawn, every one of their boundaries has to be built and kept to the rated standard.

Compartmentation

What a fire compartment is made of

Each part must hold for the same fire resistance period. The weakest part sets the real rating.

  1. WallsFire-resisting walls from floor slab to the slab above, not stopping at the false ceiling.
  2. FloorsThe slab itself, plus every hole cut through it for shafts and services.
  3. DoorsRated fire doors with closers, seals and hardware that match their test.
  4. OpeningsEvery cable, pipe and duct through a wall or floor, sealed with a tested system.
  5. JointsGaps where walls meet slabs and columns, sealed with a product that allows movement.
The rule to rememberA 120 minute wall with one open cable hole is not a 120 minute wall.
Walls and floors are usually built right. Openings are where compartments fail.

Walls, floors and doors

Walls. Compartment walls are usually built from blockwork, concrete or rated board systems. The most common fault is a wall that stops at the false ceiling. It looks complete from the room, but above the ceiling tiles there is an open void running across the building. Fire and smoke travel through that void straight past the wall. A compartment wall must run from the floor slab to the underside of the slab above.

Floors. The concrete slab between floors is normally a good fire barrier on its own. The problem is the holes cut through it: shafts for cables and pipes, openings for ducts, and sleeves for plumbing. Each one turns a solid floor into one with a chimney in it.

Doors. A fire door is tested as a complete set: the door leaf, the frame, the glass panel if any, the closer, the hinges, the seals and the gap at the edges. Remove the closer, wedge it open, or fit a different lock, and it is no longer the door that was tested.

For the numbers behind this, see our fire accident statistics for India, compiled from NCRB data.

Openings: where compartments actually fail

Walls and floors are usually built well. Then the services arrive. Electricians, plumbers, air conditioning teams and IT contractors all need to pass through compartment boundaries, and each one cuts a hole. Months or years later, other contractors cut more.

Every one of those holes has to be closed with a product tested for that situation. A cable tray through a wall needs a different seal from a single plastic pipe through a floor. A large shaft needs a different solution from a small conduit. We cover each type in our guide to service penetrations and fire stopping, and the large floor openings in shaft closing.

OpeningTypical tested solutionCommon wrong fix
Large cable or pipe shaft through a slabFire stop mortar over rebar and meshPlywood or sheet covered with cement
Cable tray through a wall, changed oftenFire safety pillows or rated barrierExpanding foam
Plastic pipe through a wall or floorIntumescent collar or wrapGap filled with ordinary sealant
Small metal pipe or conduitFire rated sealant to the tested depthCement patch with cracks
Gap at the top of a wallFire rated joint seal that allows movementRigid filler that cracks as the slab moves
One unsealed hole in a compartment floor is enough to let smoke reach the floor above in minutes. The rating of the floor around it does not matter.

Joints and gaps

Buildings move. Slabs deflect under load, and the structure expands and contracts with heat. The joint where a compartment wall meets the slab above, or where it meets a column, has to allow that movement and still stop fire. Rigid materials such as cement mortar crack. A fire rated sealant designed for movement stays sealed. We explain how to choose one in fire rated sealant.

How to check your own building

  • Find the fire compartment drawing. If nobody can, that is the first finding.
  • Open electrical and plumbing riser doors on several floors and look at the slab around the services.
  • Lift ceiling tiles where cable trays or ducts cross walls shown as rated.
  • Check that fire doors close and latch by themselves.
  • Photograph anything that looks open, with the room or grid reference in the shot.

If that produces a list, a passive fire audit will do the same across the whole building and rank what needs fixing first.

Where we fit, and where we do not

We seal the openings, joints and shafts that keep compartments working, apply intumescent coatings to steel, and audit what is already installed, with photographs of every item. We do not design fire compartmentation. That is the fire consultant's job. We do not build the walls themselves or supply fire doors. If you want to know whether your compartments are still doing their job, talk to our team.

Sources and review

National Building Code of India 2016, Part 4, Fire and Life Safety, published by the Bureau of Indian Standards. Rules and portals change, so always confirm the current requirement for your building. Last reviewed 26 October 2026 by the Simfy Firesys team.

Questions people ask
?
What is fire compartmentation as per NBC?It is the division of a building into zones bounded by fire-resisting walls, floors and doors, so fire and smoke stay in one zone for a set time. NBC 2016 Part 4 sets the requirements by building type and height.
?
What is the maximum compartment size in NBC?NBC 2016 Part 4 sets limits that depend on the occupancy, the building height and whether it is sprinklered. Your fire consultant will confirm the figure that applies to your building.
?
Do compartment walls have to go up to the slab?Yes. A compartment wall that stops at the false ceiling leaves a path for fire and smoke over the top. It must continue to the underside of the slab above, and the gap at the top must be sealed.
?
How do I check compartmentation in my building?Start with the fire compartment drawing, then look above ceilings and inside shafts where services cross rated walls and floors. A passive fire audit does this systematically with photographs.
?
What is an example of fire compartmentation?A staircase enclosed by fire rated walls with self-closing fire doors on each floor is a simple example. A fire on one floor stays out of the stair, so people can use it to escape and firefighters can use it to get in.

Reading is the cheap part.

If any of this described your building, the next step is someone with a torch and a camera walking your risers.